Air Changes

Air Changes per hour

The air changes up to eight an hour provide for removing contamination normally caused by human occupants. The higher rates of air changes provide for removing heat and steam in temperate zones. In hot climates the air changes per hour should be at least doubled.

Where smoking occurs allow twice the number of air changes.

The Table below gives a guide to the number of air changes per hour generally accepted in ventilation.


SITUATION AIR CHANGES PER HOUR
Assembly Halls 4 – 6
Bakeries 20 - 30
Banks 2 - 4
Billiard Rooms 6 - 8
Boiler House 20 - 30
Cafes & Coffee Bars 10 - 12
Canteens 4 - 6
Churches 1/2 - 1
Cinemas 10 - 15
Club Rooms 8 - 10
Dance Halls 6 - 8
Dye Works 20 - 30
Engine Rooms 20 - 30
Ensuites 15 - 20
Factories (Workshops) 6 - 10
Foundries 20 - 30
Garages 6 - 8
Hospitals (General Wards) 4 - 6
Hotel Bars 4 - 6
Kitchens (Commercial) 15 - 20
Kitchens (Domestic) 10 - 15
Laboratories 4 - 6
Lavatories 10 - 15
Laundries 20 - 30
Machine Shops 6 - 10
Offices 4 - 6
Paint Shops 30 - 60
Photographic Darkrooms 10 - 15
Pig Houses 6 - 10
Poultry Houses 6 - 10
Residences 1 - 2
Restaurants 6 - 10
School Classrooms 2 - 3
Swimming Baths 20 - 30